نسب العقوبات الملائمة لأخطار التشغيل الخاصة (GPS).
جدول رقم ( ۲ )
DEFI: Penalties for general process hazards (Dow chemical component,
المصدر :. 1976.
A)
1 -
2-
3.
-
B)
1 -
2-
3-
Process temperature :
Apply penalty when process or handling condition above flash point of material = 25% penalty.
Apply peratly when above conditions are in excess of boiling point = 60 % penalty.
Materials such as hexane, fuel oil # 1 and corbon disulphide have autoiquition.
Low Pressure:
When air leaking into the system could creat a hazard opply a 50% penalty.
Hydrogen collection systems require a 50 % No penalty if not collected.
any cacuum distillation at less than 500 mm Hgshould be penalized of 75% if air or contaminants.
C) Operation in or near flammable range :
1 -
2-
3-
D)
Storage of class 1 flammable liquids required 50 % for out door tanks (flash point below 100% °F) (37.8 °C).
For process opens class flammable limits when it is necessary to instrumentation and for nitrogen or air purg to stay and side oxplassive limits use 75%.
For process that generally operation flammable rang use a 100%. Dust explaosion hazard:
Transfering combustible dusts by air to silos, hoppears of dust collectiors, the penalty factor is based in the energypatertial of the dust, by the following table.
of
ص ٥٣