! نسب العقوبات الملائمة لأخطار التشغيل الخاصة (GPS). جدول رقم ( ۲ ) DEFI: Penalties for general process hazards (Dow chemical component, المصدر :. 1976. A) 1 - 2- 3. - B) 1 - 2- 3- Process temperature : Apply penalty when process or handling condition above flash point of material = 25% penalty. Apply peratly when above conditions are in excess of boiling point = 60 % penalty. Materials such as hexane, fuel oil # 1 and corbon disulphide have autoiquition. Low Pressure: When air leaking into the system could creat a hazard opply a 50% penalty. Hydrogen collection systems require a 50 % No penalty if not collected. any cacuum distillation at less than 500 mm Hgshould be penalized of 75% if air or contaminants. C) Operation in or near flammable range : 1 - 2- 3- D) Storage of class 1 flammable liquids required 50 % for out door tanks (flash point below 100% °F) (37.8 °C). For process opens class flammable limits when it is necessary to instrumentation and for nitrogen or air purg to stay and side oxplassive limits use 75%. For process that generally operation flammable rang use a 100%. Dust explaosion hazard: Transfering combustible dusts by air to silos, hoppears of dust collectiors, the penalty factor is based in the energypatertial of the dust, by the following table. of